Can we use protection CT for metering?
Protection Current Transformer (CT) and Metering CT are two different types of CT as per their requirement and hence design. Therefore, Protection class CT should not be used as Metering CT. Similarly, a Metering Current Transformer should not be used for protection purpose.
What is a protection CT?
The protection current transformer is used to reduce the currents in power systems, producing proportional currents in the unit’s secondary windings that remain isolated from the main circuit.
What is a metering CT?
A CT meter is a device that measures amperage in one or more conductors using sensors called current transformers (CTs). In addition to amperage, these metering devices measure voltage so they can ultimately calculate power.
What will happen if we interchange protection CT with metering CT?
Metering current transformers are designed to be within quite accurate values up to say two x rated current, and down to <0.01 x rated. Consequently a protection relay connected to a metering current transformer will get a heavily saturated waveform during fault conditions and it won’t work properly.
What is a CT cabinet used for?
The CT cabinets are an essential part of electrical metering systems and are used both indoor and outdoor and in homes and industries. They are the enclosures in which the current transformers are mounted in. The cabinets are also made to prevent electrocution by setting up a physical barrier.
What does CT class mean?
CT Class Rating is a letter that designates the application for which the CT is rated. Metering CTs are designated with the letter B. Relaying CTs have several different letter designations: C: The CT has low leakage flux. (Accuracy can be calculated before manufacturing.)
How does the CT used for protection is different from CT used for metering State two major differences?
Current transformers are used for both metering and protection purposes. By reduce the power system primary current to lower value CT is used for measuring or metering purpose. By permit the use of standard current rating for secondary equipment CT is used for Protection purpose.
What is knee point?
The knee point is defined as the voltage at which a 10\% increase in applied voltage increases the magnetizing current by 50\%. For voltages greater than the knee point, the magnetizing current increases considerably even for small increments in voltage across the secondary terminals.
What is a CT chamber?
A CT Chamber houses current transformers for low voltage metering applications. They are required to transform high voltage to low voltage for your multi-occupancy residential or commercial property.
What is the difference between CT and metering CT?
Protection Current Transformer (CT) and Metering CT are two different types of CT as per their requirement and hence design. Therefore, Protection class CT should not be used as Metering CT. Similarly, a Metering Current Transformer should not be used for protection purpose. Let the discuss the reason behind this.
Can protection class CT be used as metering CT?
Therefore, Protection class CT should not be used as Metering CT. Similarly, a Metering Current Transformer should not be used for protection purpose. Let the discuss the reason behind this. Why can’t we use Protection CT for Metering Purpose?
What is the difference between CT and CT for measurement and protection?
By reduce the power system primary current to lower value CT is used for measuring purpose.By permit the use of standard current rating for secondary equipment CT is used for Protection purpose.The CTs used for measurement and protection purposes have different properties.Following are the basic differences between two. 1.
What happens when metering CT secondary is connected to protection relay?
Let us now assume that this metering CT secondary is connected to protection relay. Under fault condition, the CT core will saturate and hence its secondary current output will be heavily distorted. Under such condition, it may happen that the relay may not operate. Thus, the power system stability will be compromised.